Search Contract Opportunities

Scott Inn HVAC Maintenance

ID: FA440724LW08-ScottInnMaintenance • Type: Solicitation

Description

THE FOLLOWING EQUIPMENT WILL BE COVERED FOR MAINTENANCE BY THE CONTRACTOR:

4- Mod Con boilers for H.P loop
2-Cooling tower pumps
1-BAC cooling tower
2-Condenser pumps
4-Chilled water pumps
4-Domestic hot water heaters
1-Multi stack chiller
1-Trane rooftop
1-Innovent Air handler
(see attachment 1)

THE FOLLOWING SERVICES WILL BE PERFORMED BY THE CONTRACTOR FOR LISTED EQUIPMENT:

1. Contractor will service packaged rooftop units quarterly to include:
a. Check the refrigerant charge
b. Lubricate motors and bearing as recommended by the manufacturer
c. Check belts for excessive wear and fatigue, adjust tension, replace quarterly,
customer supplied
d. Visually inspect electrical components
e. Check major electrical connections, tighten as required
f. Record volt/amps of major electrical components
g. Check crankcase heater
2. Contractor will service heating boilers to include:
a. Inspect and clean the waterside quarterly
b. Inspect economizers, deaerators, and condensate receivers quarterly
c. Check the refractory quarterly
d. Burner inspection
e. Inspect controls for proper operation
f. Check the fluid levels on hydraulic valves and repair any signs of leakage
g. Check filters and clean or replace them quarterly
h. Check boiler feedwater and recirculation pumps
i. Empty and wash out condensate receivers and make an internal inspection
j. Check electrical connections on starters and relays for tightness
k. Inspect and clean the fireside quarterly
l. Recommended PM kits will be invoiced separately if needed

3. Contractor will service chillers to include:
a. Clean condenser tube bundles annually
b. Check coupling bolts
c. Tighten main starter and control panel connections
d. Check all safeties
e. Check operating controls
f. Check refrigerant and leak check machine
g. Log all operating conditions after unit stabilizes
h. Calibrate stater sensor annually
i. Contractor is to be certified on Dan Foss compressors

4. Contractor will service cooling towers to include:
a. Lubricate fan and motor bearings as per Manufacturer's recommendation
b. Change V-belts customer supplied
c. Check motor pulley, motor mounts, and bearings; adjust as required
d. Inspect electrical connections, contactors, relays and operating/safety controls
e. Check motor operating conditions
f. Clean electronic eye system for proper operation
g. Clean basin (bottom of cooling tower) and sump tank annually
h. Contractor must be familiar with Metasys system

5. Contractor will service pump skids to include:
a. Lubricate pump bearings quarterly
b. Lubricate motor bearings quarterly
c. Check motor mounts and vibration pads
d. Visually check pump alignment and coupling condition
e. Check motor operating conditions
f. Inspect electrical connections and contactors
g. Inspect mechanical seals
h. Check suction and discharge pressure
i. Check packing or mechanical seal for leaks

6. Contractor will service the gas-fired water heater for domestic heating to include:
a. Flush and clean two (2) times per year water only flush
b. Lubricate the fan motor as recommended
c. Check and test the pilot, ignition and safety controls

7. Contractor will service air handling units to include:
a. Lubricate motors and bearing as recommended by the manufacturer
b. Visually inspect electrical components
c. Check major electrical connections, tighten as required
d. Record volt/amps of major electrical components
e. Replace air filters two (4) times per year supplied by customer
f. Inspect heat wheel and v-belt to include proper maintenance and cleaning

8. Additional Work In Scope:

a. Scheduled Repairs - Deficiencies discovered during inspections, and not covered by the annual maintenance fee will be corrected on a time and material basis. All cost associated with any deficiencies will be discussed with the customer and contractor is required to obtain prior approval before any work is performed.

i. Lodging Manager
ii. Assistant Lodging Manager
iii. Operations Manager
iv. Maintenance Supervisor
v. Maintenance Worker
vi. Contracting Officer

9. Service Intervals and Payment Schedules:

a. Contractor will perform four (4) inspections annually; one (1) inspection each quarter. A written report will be submitted to customer following each inspection. The report will detail the work performed during the inspection and identify areas of concern, together with recommendations for repairs.

b. Annual maintenance fee will be invoiced in four (4) installments at time of inspection.

Background
The solicitation is for HVAC unit maintenance, repair, and inspection at Scott Inn, Scott AFB IL. The contract is issued by the USAF AMC 375 FSS/FSVL. The performance work statement outlines the specific equipment and services to be covered by the contractor.

Work Details
The contractor will cover maintenance for various equipment including Mod Con boilers, cooling tower pumps, BAC cooling tower, condenser pumps, chilled water pumps, domestic hot water heaters, multi stack chiller, Trane rooftop, and Innovent Air handler. Services to be performed include servicing packaged rooftop units, heating boilers, chillers, cooling towers, pump skids, gas-fired water heater for domestic heating, air handling units, and scheduled repairs. The contractor is required to perform four inspections annually and submit a written report after each inspection.

Period of Performance
Current as of 27 March 2024

Place of Performance
Scott Inn 460 West Winters Street Bldg 1812 Scott AFB IL 62225

Overview

Response Deadline
July 25, 2024, 11:00 a.m. EDT Past Due
Posted
July 11, 2024, 2:07 p.m. EDT
Set Aside
Small Business (SBA)
Place of Performance
Scott AFB, IL 62225 United States
Source
SAM

Current SBA Size Standard
$19 Million
Pricing
Likely Fixed Price
Est. Level of Competition
Average
Est. Value Range
Experimental
$50,000 - $100,000 (AI estimate)
On 7/11/24 Air Mobility Command issued Solicitation FA440724LW08-ScottInnMaintenance for Scott Inn HVAC Maintenance due 7/25/24. The opportunity was issued with a Small Business (SBA) set aside with NAICS 238220 (SBA Size Standard $19 Million) and PSC J041.
Primary Contact
Name
Neil Calica   Profile
Phone
(618) 256-9268

Secondary Contact

Name
Chrissina Dural   Profile
Phone
(618) 576-3139

Documents

Posted documents for Solicitation FA440724LW08-ScottInnMaintenance

Question & Answer

Incumbent or Similar Awards

Contracts Similar to Solicitation FA440724LW08-ScottInnMaintenance

Potential Bidders and Partners

Awardees that have won contracts similar to Solicitation FA440724LW08-ScottInnMaintenance

Similar Active Opportunities

Open contract opportunities similar to Solicitation FA440724LW08-ScottInnMaintenance